Calculate the rating for multiple circuits in the same duct

Modified on Wed, 21 Jul 2021 at 10:56 AM

This problem is not covered directly by the IEC Standards (i.e. they only cover the rating for 1 circuit in a duct).  To solve this problem using the IEC equations is a multi-step process using Cable HV Software.


This method has the following assumptions:

  • Cables are the same type.
  • Circuits are equally loaded.



Example calculation - 3 circuits installed in the same buried duct

In this example we will be calculating the current rating for multiple circuits (3 circuits) installed inside the same buried duct.


Step 1: Calculate the current rating for a single circuit (3 cables) buried in the same duct.


Make sure the duct size being modelled is the same duct size which will house the multiple circuits.


Rating 1 in this example = 517.38 A

This is the current rating for a single circuit installed in the same duct.

Next we will derive a custom derating factor for multiple circuits.



Step 2: Calculate the current rating for a single circuit installed in air.


Use the installation method called "Three cables in trefoil, clipped direct" (as shown) to include that while installed inside a duct the cables will be touching the inside walls of the duct.


Rating 2 in this example = 605.96 A

This is the current rating for a single circuit installed in air.



Step 3: Calculate the current rating for multiple circuit installed in air In Groups.


Use the installation method called "Side by side_3 trefoils" (as shown) and make sure the Clearance, e = 0 m to include the thermal proximity effect (mutual heating between the circuits in air).


Rating 3 in this example = 578.8 A

This is the current rating for 3 circuits installed (touching) in air in a group as they would be inside the duct together.




Final step: Calculate the derating factor for the groups in air and apply it to the buried case rating.


Use the installation method called "Side by side_3 trefoils" (as shown) and make sure the Clearance, e = 0 m to include the thermal proximity effect (mutual heating between the circuits in air).


This is the current rating for 3 circuits installed (touching) in air in a group as they would be inside the duct together.


The final rating for multiple circuits installed in one duct = (Rating 3/ Rating 2) x Rating 1  


Where Rating 3 / Rating 2 (578.8 A/605.96 A=0.9552) is the derating factor to be applied to Rating 1.


Final current rating of a circuit installed inside the same duct (3 circuits in total) = 494.94 A


Was this article helpful?

That’s Great!

Thank you for your feedback

Sorry! We couldn't be helpful

Thank you for your feedback

Let us know how can we improve this article!

Select atleast one of the reasons
CAPTCHA verification is required.

Feedback sent

We appreciate your effort and will try to fix the article