Increase the number of circuits to reduce the active cable size

Modified on Mon, 30 Aug 2021 at 01:21 PM

Using the cable sizing calculator in the cloud-based Cable Pro Web software, you can manually increase the no. of parallel circuits to reduce the cable size.


The steps are as follows:


Step 1 - Enter all inputs as usual, such as load current, length of run, installation method etc.


Step 2 - After obtaining the results, change the mode of Active size to be 'MANUAL' in the 'Cable size' tab.


Step 3 - Increase the value of No. of circuits.


Step 4 - Select the active cable size from the dropdown to achieve compliance (such as the voltage drop limit).

Note that compliance checks of current-carrying capacity, voltage drop limits, fault loop impedance and short-circuit ratings are still being checked in manual mode. 


In the example below, on the left-hand side is shown the minimum compliant Auto result was a single 50 mm2 cable circuit.  Then on the right-hand side the user has manually selected two circuits of 16 mm2 cable.  Both are compliant solutions.



Was this article helpful?

That’s Great!

Thank you for your feedback

Sorry! We couldn't be helpful

Thank you for your feedback

Let us know how can we improve this article!

Select atleast one of the reasons
CAPTCHA verification is required.

Feedback sent

We appreciate your effort and will try to fix the article